Modulon NH Plus is the 3-phase UPS with the high efficiency, modular construction and the scheme of parallel reservation of N+X.

Efficiency is more than 94%. Thanks to the scheme of parallel reservation of N+X, NH provides reliable protection for data processing centers, the industrial, telecommunication and medical equipment and also any crucial applications.

File:Modulon NH Plus Series UPS 20 120 kVA.jpg

Modulon NH Plus

Name Article
Power module 20 kVA for NH-Plus Series 3915100486-S
System NH-Plus 80 kVA chassis GES803HP3312035  
System NH-Plus 120 kVA chassis GES124HP3312035
Battery module 40Ah for NH-Series original (without batteries) GES401H04000035
The NH-series 20kVA UPS with joint stock bank (40x12V9Ah) GES203NH3302101
The NH-Series 40 kVa UPS with  batteries GES403NH3302101

 

Possibilities of Delta NH-Plus

From 20 to 480 kVA (4 x 120 kVA in a parallel).

  • Double reservation at the level of modules and a system.
  • Reservation of power supply of secondary chains and control circuits provide high reliability.
  • The built-in mechanical and electronic switches of a bypass for service maintenance.

  • Modular construction provides simplicity in service and further expansion.
  • Multilingual LCD display.
  • Two Smart slot connectors and 6 programmable exits like "dry contact".
  • Standard and universal types of battery cabinets for a wide choice of time of providing back supply and economy of the taken place.

High coefficient of input power (pf> 0.99) and small harmonic distortions of an input current (iTHD <3%). Economy of energy thanks to high efficiency (94%) even at 25% to loading. Is suitable for joint work with the diesel generator.

Technical characteristics of the Delta NH Plus UPS of 20-120 kVA:
Model NHP-20K NHP-40K NHP-60K NHP-80K NHP-100K NHP-120K
Form voltage output Sinusoid
Rated power of kVA/kW 20/16(18) 40/32(36) 60/48(54) 80/64(72) 100/80 (90) 120/96 (108)
Login Rated tension Three-phase 220/380B; 230/400B; 240/415B
Range tension At 208-300B loading from 70% up to 100% it is proportional, at 301-477B loading of 100%
Rated frequency 50 Of Hz or 60 Hz
Range frequencies 50-60gts ±5Гц
Coefficient capacities > 0,99
Input connectors Terminal block
Protective devices 50A 75A 125A 160A 200A 250A
Connected a cable 10 mm2 16 mm2 35 mm2 2*25 mm2 2*35 mm2 3*35 mm2
Exit Rated tension Three-phase 220/380B; 230/400B; 240/415B
Adjustment tension +/- 1%
Harmonious distortions Less 3% at linear loading
Capability to an overload Up to 125% in a current of 10 min., <150% 1 min.
Output frequency 50 Of Hz or 60 Hz, +/-0.1 Hz
Coefficient capacities 0.8 (to 0.9 at a temperature less +25ºС)
Cross factor 3:1
Output connectors Terminal block
Protective devices 50A 75A 125A 160A 200A 250A
Connected a cable 10 mm2 16 mm2 35 mm2 2*25 mm2 2*35 mm2 3*35 mm2
EFFICIENCY On-line mode 94%
ECO mode 97%
Battery Type and number of batteries Lead-acid 40 pieces.
Tension chains ±240В direct current
Current charger 5A 10A 15A 20A 25A 30A
Tension at a charge Floating charge ±272В
Input connectors Terminal block
Protective devices DC 500B 63A DC 500B 125A DC 500B 160A DC 500B 250A DC 500B 320A DC 500B 320A
Connected a cable 25 mm2 25 mm2 2*25 mm2 2*25 mm2 2*35 mm2 3*35 mm2
Acoustic noise < 70 dB(A)
Indicators and display LED indicators and multilingual display
Communication interfaces Consecutive RS-232 port – 2, REPO Port – 1, and also the slot under communication cards: USB, Web/SNMP, Modbus
Manual service bypass yes yes yes yes yes yes
Protection on a bypass input 50A 75A 125A 160A 200A 250A
Opportunity parallel operation Up to 4 pieces.
Insulating transformer no
Dimensions, mm 520*910*1165 520*975*1650
Weight, kg 125 175 210 244 339 379td>
Parameters Working temperature From 0ºС to +40ºС
Temperature storages From -15ºС to +50ºС
Relative humidity 5% -95% without formation of condensate

Delta Electronics: NH Plus

NH Plus is the UPS of the next generation with the high efficiency, "hot" replacement of power modules and the scheme of parallel reservation of N+X from Delta Electronics company.

Scope of application: DPCs, telecommunications, industry, networks, bezopasnost, laboratories, medicine, subway.

Specific Features

  • From 20 to 480 kVA (4 x 120 kVA in a parallel).
  • Reservation at the level of the module and a system.
  • "Hot" replacement of power modules without interruption power supply of loading.
  • Reservation of auxiliary power sources.
  • The built-in mechanical and electronic bypass for service maintenance.
  • Modular construction provides simplicity in service and flexibility in increase in power.
  • Multilingual LCD display and LED indicators.
  • Two Smart slot connectors and 6 programmable exits like "dry contact".
  • Battery offices of the increased capacity for increase in time of back power supply. (Option)
  • High coefficient of input and power output (pf> 0.99) and small harmonic distortions of an input current (iTHD < 3 %), позволяют сэкономить на этапе начальных инвестиций.
  • Economy of energy thanks to high efficiency (94%).

File:NH plus 03 500w 1054647 snapshot rdax 428x500.jpg

Specifications

NHP-20K/NHP-40K/NHP-60K/NHP-80K/NHP-100K/NHP-120K model

Power kVA

  • NHP-20K: 20 kVA
  • NHP-40K: 40 kVA
  • NHP-60K: 60 kVA
  • NHP-80K: 80 kVA
  • NHP-100K: 100 kVA
  • NHP-120K: 120 kVA

kW *

  • NHP-20K: 18 kW (< 25°C) / 16 кВт(< 40°C)
  • NHP-40K: 36 kW (< 25°C) / 32 кВт(< 40°C)
  • NHP-60K: 54 kW (< 25°C) / 48 кВт(< 40°C)
  • NHP-80K: 72 kW (< 25°C) / 64 кВт(< 40°C)
  • NHP-100K: 90 kW (< 25°C) / 80 кВт(< 40°C)
  • NHP-120K: 108 kW (< 25°C) / 96 кВт(< 40°C)

Login

  • Rated voltage is 380 V / 220 V, 400 V / 230 V, 415 V / 240 V Lanes of current (3 phases, 4 conductors plus grounding)
  • Range of tension is 208 V ~ 477 V (phase phase) / 120 V ~ 276 V (phase neutral) **
  • Total harmonic content of current < 3 % (при полной нагрузке)
  • Electrical power factor> 0.99
  • Frequency is 50 Hz / 60 Hz ± 5 Hz

Exit

  • Voltage is 380 V / 220 V, 400 V / 230 V, 415 V / 240 V Lanes of current (3 phases, 4 conductors plus grounding)
  • Total coefficient. tension harmonics < 3 % (при линейной нагрузке)
  • Voltage regulation limits ± 1% (statich.)
  • Frequency is 50 Hz / 60 Hz
  • Limits of regulation of frequency ± 0.05 Hz (from the built-in generator)

± 5 Hz (synchronization from entrance network with a step to 0.1 Hz)

  • Overload capacity ≤ 125%: 10 minutes

≤ 150%: 1 minute

Interfaces

  • Standard RS232 × 1, slots of SNMP × 2, exits with dry

contacts × 6, inputs with dry contacts × the 2nd inputs of temperature sensors of a battery office × 4, an input of a status of a battery office × 1, parallel ports × 1, REPO (abnormal remote power-off)

  • Peripheral devices of management and Plath's control by SNMP, Modbus payment, payment of relay inputs and exits, block of sensors

environment, hub SNMP + 5 ports, battery temperature sensor, set of the battery temperature sensor, signal cable of a battery cabinet

Compliance to standards

Security and EMS of CE, EN62040-1, EN62040-2 Class A

Other

  • Parallel reservation and expansion - modular and system reservation, at most 4 offices in a parallel up to 480 kVA
  • Emergency power off - local and remote
  • Statistical memory for the working magazine - 500 records

EFFICIENCY

  • Normal mode of 94%
  • Economy mode of 97%

Environment

  • Working temperature 0 ~ 40ºC
  • Relative humidity 0 ~ 90% (without formation of condensate)
  • Noise level (at distance of 1 m)
  • NHP-20K: 65 dB(A)
  • NHP-40K: 68 dB(A)
  • NHP-60K: 68 dB(A)
  • NHP-80K: 70 dB(A)
  • NHP-100K: 72 dB(A)
  • NHP-120K: 73 dB(A)

Total characteristics

  • The UPS Overall dimensions (Highway x In x)
  • NHP-20K ~ 80K: 520 x 910 x 1165 mm
  • NHP-100K ~ 120K: 520 x 975 x 1695 mm

Battery office Overall dimensions (Highway x In x) - NHP-20K ~ 80K: 520 x 850 x 1165 mm (26 Ah x of 40 pieces)

NHP-100K ~ 120K: 520 x 975 x 1695 mm (40 Ah x of 40 pieces)

UPS Weight

  • NHP-20K: 170 kg
  • NHP-40K: 200 kg
  • NHP-60K: 230 kg
  • NHP-80K: 260 kg
  • NHP-100K: 350 kg
  • NHP-120K: 380 kg

  • The UPS this parameter can be changed
    • Work in the range of voltage of 208 ~ 300/120 ~ 173 V Lanes of current are allowed at loading of the UPS of 70-100%.