Customers: Petrocommerce bank
Contractors: IBS Platformix Product: DPC Projects of creation and upgradeProject date: 2014/09
|
Goals and Objectives
Active rates of business development of Bank and, as a result, upgrade of IT infrastructure resulted in need of creation of a new modern data processing center. Specialists of IBS Platformix company were involved to the solution of this question. The task – to develop in the selected premises infrastructure of reserve DPC according to requirements of the existing regulating documents for placement in it server and telecommunication equipment was set for the system integrator.
Project Progress
The complex project included all range of services on creation of IT infrastructure: project, installation, construction works and also delivery, setup and start of the equipment in operation. For new DPC modern engineering infrastructure which part the following systems were was created:
- system of raised floors;
- power supply system and electric lighting;
- the system of the guaranteed uninterrupted power supply;
- system of precision conditioning;
- structured cabling system;
- system of early detection of the fire and gas fire extinguishing;
- monitoring system and control of parameters of the environment.
Result
Within the project migration of the structured cable network from former server was performed. The network included trunk lines of communication from each floor of the building and telephone multi-pair cables. Also secondary circuits between two server were organized. The telephone network on an object is built using UPATS of Coral III. This system has high flexibility (one installation can service from 30 to 4000 ports) and has great opportunities for expansion of a system. The project provides additional building of main telephone cables from the premises old server in the premises of reserve DPC. At construction of a conditioning system the industrial Liebert HPM S23DA conditioners providing indoors air temperature on an input in equipment cabinets within 21-23 °sa air humidity within 40-50% at round-the-clock operation of the equipment are used. Moisture condensation is excluded under any conditions.
4 conditioners of direct expansion to 40 kW of the taken-away heat everyone, with reservation of N+1 are used to cooling of equipment cabinets. 2 ceiling conditioners of the channel Mitsubishi Heavy type, with the power up to 20 kW taken-away heat everyone, with reservation 2N are used to cooling of the equipment of uninterrupted power supply. Technology premises of DPC are equipped with modular installations of automatic gas fire fighting. As a subsystem of the guaranteed power supply diesel generator sets of Gesan DVA 410 E company with a reserve capacity of 378 kVA which differ in high reliability thanks to use of engines of industrial appointment as svodyany cooling with inizky rotating speed are used. Monitoring of the environment is provided by the APC NetBotz system based on the Rack Monitor 570 network controller. NetBotz provides effective control of parameters of engineering infrastructure, the analysis of situations and the operational notification of personnel for the purpose of prevention of violations in work or idle time of IT infrastructure.
"One izklyuchevy tasks for any serious financial institution reliable reservation of all information resources is. Suchetom of increase in information volumes an ivnedreniye of new IT services we had a need of a vsozdaniya of full-fledged reserve DPC which would provide us reducing ability in case of any emergencies, - a kommentiruyetdirektor of department of information technologies of Petrocommerce Bank Andrey Belozerov. – We could implement it using IBS Platformix system integrator. The unrolled engineering systems guarantee continued operation and fault tolerance of key business processes of bank and also ensure physical security of all IT infrastructure. In the project the possibility of upgrade and building of the existing complex of the engineering equipment is put that will allow to avoid possible difficulties at the subsequent operation of DPC".